Gree — Fault Codes
40 codes
GMV5 / GMV5E
E3
— System low pressure protection
E4
— Compressor high discharge temperature protection
F1
— High pressure sensor malfunction
F3
— Low pressure sensor malfunction
GMV6
C0
— Communication malfunction between indoor and outdoor units and between the indoor unit and its wired controller (per manual: no communication for 30 seconds).
C1
— Communication malfunction between the main control and the DC-DC controller.
C2
— Communication malfunction between the main control and the inverter compressor driver (fault when the driver is not detected for 30 consecutive seconds).
E0
— Malfunction of the outdoor unit (ODU) – error-table entry.
E1
— High pressure protection triggered.
E2
— Protection against too low compressor discharge temperature: the unit stops when the difference between the discharge temperature and the temperature at the high pressure is below 10 °C (manual).
E5
— Insufficient refrigerant in system.
E6
— Oil inadequately returning to compressor.
E7
— Outdoor control board internal error.
F0
— Main board of the outdoor unit is poor: the address, memory or clock chip cannot be read properly.
F2
— Wired remote controller link failure.
F4
— Indoor unit address conflict or misconfiguration.
F5
— Malfunction of the discharge temperature sensor of compressor 1.
H0
— Malfunction of the fan drive board (parent code on the indoor unit's wired controller); the specific fault is shown on the 2-digit LED of the outdoor unit's main board.
H1
— Fan drive board operates abnormally (parent code on the indoor unit's wired controller); the specific fault is shown on the 2-digit LED of the outdoor unit's main board.
H3
— Reset protection of the fan drive module (code H3 on the 2-digit LED of the outdoor unit's main board; sub-code of H0).
H4
— Drive PFC protection of the fan.
H5
— Over-current protection of the inverter fan (shown on the 2-digit LED of the outdoor unit's main board; sub-code of H1).
H6
— Drive IPM module protection of the fan (shown on the 2-digit LED of the outdoor unit's main board; sub-code of H1).
H8
— Drive IPM high-temperature (over-temperature) protection of the fan (shown on the 2-digit LED of the outdoor unit's main board; sub-code of H0).
H9
— Loss of synchronization (desynchronizing) protection of the inverter fan (shown on the 2-digit LED of the outdoor unit's main board; sub-code of H0).
P0
— Malfunction of the compressor drive board (parent code on the indoor unit's wired controller); the specific fault is shown on the 2-digit LED of the outdoor unit's main board.
P1
— Compressor drive board operates abnormally (parent code on the indoor unit's wired controller); the specific fault is shown on the 2-digit LED of the outdoor unit's main board.
P2
— Input voltage protection of the compressor drive board (parent code on the indoor unit's wired controller); the specific fault is shown on the 2-digit LED of the outdoor unit's main board.
P3
— Reset protection of the compressor drive module (shown on the 2-digit LED of the outdoor unit's main board; sub-code of P0).
P4
— Drive PFC protection of the compressor.
P5
— Over-current protection of the inverter compressor (shown on the 2-digit LED of the outdoor unit's main board; sub-code of P1).
P6
— Drive IPM module protection of the compressor (shown on the 2-digit LED of the outdoor unit's main board; sub-code of P1).
P7
— Malfunction of the drive temperature sensor of the compressor drive board (shown on the 2-digit LED of the outdoor unit's main board; sub-code of P0).
P9
— Loss of synchronization (desynchronizing) protection of the inverter compressor (shown on the 2-digit LED of the outdoor unit's main board; sub-code of P0).
Pb
— Inverter DC bus overvoltage.
Pc
— Malfunction of the current detection circuit of the compressor drive (listed in the manual as “PC” with a capital C; shown on the 2-digit LED of the outdoor unit's main board; sub-code of P0).
U2
— Wrong setting of ODU's capacity code/jumper cap
U3
— Power phase sequence protection
U4
— Refrigerant-lacking protection
UE
— Charging of refrigerant is invalid