Fault Codes / Gree / H5
GR
Gree H5
Medium
GMV6 — Over-current protection of the inverter fan (shown on the 2-digit LED of the outdoor unit's main board; sub-code of H1).
Gree H5: Over-current protection of the inverter fan (shown on the 2-digit LED of the outdoor unit's main board; sub-code of H1). This fault usually isn't an immediate stop, but should be checked soon.
Possible causes
- Poor contact of the fan's UVW cables.
- The fan is damaged.
- The blades are stuck (blocked or rusted motor shaft).
- The fan drive board operates improperly.
Check steps
- Check that the U, V and W phases of the fan leads are connected properly.
- Check the winding resistance of each fan phase (typical per manual: below 10 Ω, “generally”), that the values are equal, and the insulation of the windings to earth (typical: above 2 MΩ); if abnormal: replace the fan.
- Check whether the blades are stuck due to foreign matter or a rusted motor shaft; remove foreign matter.
- If other faults occur at the same time (e.g. HJ, H6, H9): replace the faulty fan; otherwise the fan drive board is abnormal – replace it.
Affected parts
- Lüfter (Außengerät)
- Fan-PCB
Safety note
Manufacturer warning (manual PDF p. 12): before performing operations on the unit (such as commissioning, maintenance and repair), shut the unit down and cut off the power; use a suitable instrument to ensure that the voltage at the power input terminals is zero and that the power indicator on the main board is off. Otherwise an electric shock or injury may be caused. Manufacturer note (ibid.): in standby the power indicators on the main board and the drive board are on. General safety note (not from the manufacturer's manual): secure against reconnection. Lit or unlit indicators alone are no proof of absence of voltage. Dangerous voltage (DC bus) may remain on the drive board/IPM after switch-off; the manual gives no general discharge time. The absence of voltage must be confirmed by measurement on site by a qualified electrician or specialist contractor. The steps reproduce the manufacturer's troubleshooting and are not a binding work instruction; any parts replacement is decided on site by the specialist contractor/Meister. Winding and insulation measurement: at this point the manual does not specify the test voltage, the instrument or disconnecting the leads from the drive board – to be determined by the specialist contractor; applying an insulation test voltage to a connected drive board can damage it. The resistance figures are typical manufacturer values (“generally”/“normally”), not fixed limits. Before reaching into the fan blades make sure the fan is stationary and cannot start automatically (crushing and cutting hazard).
Source: Gree GMV6 DC Inverter VRF Units Service Manual GC202005-I (AB, 380-415V 3N~ 50/60Hz, GMV-224…615WM/H-X), Fehlerliste PDF s.70-73, Abschnitt 2.82 PDF s.131 (basılı 129); Warnhinweis PDF s.12 (basılı 10)