Fault Codes / Gree / E2
GR
Gree E2
High
GMV6 — Protection against too low compressor discharge temperature: the unit stops when the difference between the discharge temperature and the temperature at the high pressure is below 10 °C (manual).
Gree E2: Protection against too low compressor discharge temperature: the unit stops when the difference between the discharge temperature and the temperature at the high pressure is below 10 °C (manual). This fault noticeably affects operation.
Possible causes
- The compressor's discharge temperature sensor operates improperly.
- The indoor unit's electronic expansion valve (EEV) operates improperly in cooling mode.
- The outdoor unit's EEV operates improperly in heating mode.
- Excessive refrigerant in the unit.
Check steps
- Check that the discharge-pipe and shell-top temperature sensors of each compressor are installed firmly and the protective sponge is fastened; check the resistance against the sensor's temperature-resistance table, otherwise replace the sensor.
- Cooling mode: first check the indoor unit's EEV – check the coil connection, power the unit off and on and observe the resetting action. Unable to reset: replace the coil or the main board; resets normally but the problem persists: replace the EEV.
- Then check the outdoor subcooler EEV: check the coil connection, power the unit off and on and observe the resetting action (the manual states no further conclusion here).
- Heating mode: first check the outdoor unit's EEV – check the coil connection, power off and on, observe the resetting action. Unable to reset: replace the coil or the main board; resets normally: inspect other parts of the unit.
- Check whether the refrigerant charge matches the design requirements; excessive refrigerant can trigger the protection. Solution per manual: add refrigerant in accordance with the design requirements.
Affected parts
- Druckgasfühler
- Expansionsventil (EEV)
- EEV-Spule
- Hauptplatine
Safety note
Manufacturer warning (manual PDF p. 12): before performing operations on the unit (such as commissioning, maintenance and repair), shut the unit down and cut off the power; use a suitable instrument to ensure that the voltage at the power input terminals is zero and that the power indicator on the main board is off. Otherwise an electric shock or injury may be caused. Manufacturer note (ibid.): in standby the power indicators on the main board and the drive board are on. General safety note (not from the manufacturer's manual): secure against reconnection. Lit or unlit indicators alone are no proof of absence of voltage. Dangerous voltage (DC bus) may remain on the drive board/IPM after switch-off; the manual gives no general discharge time. The absence of voltage must be confirmed by measurement on site by a qualified electrician or specialist contractor. The steps reproduce the manufacturer's troubleshooting and are not a binding work instruction; any parts replacement is decided on site by the specialist contractor/Meister. Work on the refrigerant circuit (e.g. charge, EEV, compressor) only by appropriately certified personnel in accordance with the applicable regulations; do not vent refrigerant to the atmosphere – recover it.
Source: Gree GMV6 DC Inverter VRF Units Service Manual GC202005-I (AB, 380-415V 3N~ 50/60Hz, GMV-224…615WM/H-X), Fehlerliste PDF s.70-73, Abschnitt 2.58 PDF s.107-108 (basılı 105-106); Warnhinweis PDF s.12 (basılı 10)