Fault Codes / Gree / E2

GR

Gree E2

High

GMV6 — Protection against too low compressor discharge temperature: the unit stops when the difference between the discharge temperature and the temperature at the high pressure is below 10 °C (manual).

Gree E2: Protection against too low compressor discharge temperature: the unit stops when the difference between the discharge temperature and the temperature at the high pressure is below 10 °C (manual). This fault noticeably affects operation.

Possible causes

Check steps

Affected parts

Safety note

Manufacturer warning (manual PDF p. 12): before performing operations on the unit (such as commissioning, maintenance and repair), shut the unit down and cut off the power; use a suitable instrument to ensure that the voltage at the power input terminals is zero and that the power indicator on the main board is off. Otherwise an electric shock or injury may be caused. Manufacturer note (ibid.): in standby the power indicators on the main board and the drive board are on. General safety note (not from the manufacturer's manual): secure against reconnection. Lit or unlit indicators alone are no proof of absence of voltage. Dangerous voltage (DC bus) may remain on the drive board/IPM after switch-off; the manual gives no general discharge time. The absence of voltage must be confirmed by measurement on site by a qualified electrician or specialist contractor. The steps reproduce the manufacturer's troubleshooting and are not a binding work instruction; any parts replacement is decided on site by the specialist contractor/Meister. Work on the refrigerant circuit (e.g. charge, EEV, compressor) only by appropriately certified personnel in accordance with the applicable regulations; do not vent refrigerant to the atmosphere – recover it.

Source: Gree GMV6 DC Inverter VRF Units Service Manual GC202005-I (AB, 380-415V 3N~ 50/60Hz, GMV-224…615WM/H-X), Fehlerliste PDF s.70-73, Abschnitt 2.58 PDF s.107-108 (basılı 105-106); Warnhinweis PDF s.12 (basılı 10)

Reviewed by Anıl Güzeldemir — in the refrigeration machine room since 2005, developer of Enthalio.

Look up in Enthalio →

Related fault codes

High pressure protection triggered.E1 Malfunction of the outdoor unit (ODU) – error-E0 Insufficient refrigerant in system.E5 Oil inadequately returning to compressor.E6 Outdoor control board internal error.E7 Main board of the outdoor unit is poor: the adF0