Fault Codes / Gree / F0
GR
Gree F0
High
GMV6 — Main board of the outdoor unit is poor: the address, memory or clock chip cannot be read properly.
Gree F0: Main board of the outdoor unit is poor: the address, memory or clock chip cannot be read properly. This fault noticeably affects operation.
Possible causes
- Abnormal address chip.
- Abnormal memory chip.
- Abnormal clock chip.
Check steps
- Using the commissioning software, check whether a system clock exception is also generated; if yes: replace the CPU (small board).
- If the problem is not solved after replacing the CPU, the manual's flowchart provides for replacing the compressor drive board. The branching of the flowchart is ambiguous in the manual – have the sequence confirmed on site by the specialist contractor/Meister.
- If the address and memory chips are abnormal: replace the main control board.
Affected parts
- CPU
- Hauptplatine Außengerät
- Inverter-Platine
Safety note
Manufacturer warning (manual PDF p. 12): before performing operations on the unit (such as commissioning, maintenance and repair), shut the unit down and cut off the power; use a suitable instrument to ensure that the voltage at the power input terminals is zero and that the power indicator on the main board is off. Otherwise an electric shock or injury may be caused. Manufacturer note (ibid.): in standby the power indicators on the main board and the drive board are on. General safety note (not from the manufacturer's manual): secure against reconnection. Lit or unlit indicators alone are no proof of absence of voltage. Dangerous voltage (DC bus) may remain on the drive board/IPM after switch-off; the manual gives no general discharge time. The absence of voltage must be confirmed by measurement on site by a qualified electrician or specialist contractor. The steps reproduce the manufacturer's troubleshooting and are not a binding work instruction; any parts replacement is decided on site by the specialist contractor/Meister.
Source: Gree GMV6 DC Inverter VRF Units Service Manual GC202005-I (AB, 380-415V 3N~ 50/60Hz, GMV-224…615WM/H-X), Fehlerliste PDF s.70-73, Abschnitt 2.61 PDF s.111 (basılı 109); Warnhinweis PDF s.12 (basılı 10)