Gree C2
High
GMV6 — Communication malfunction between the main control and the inverter compressor driver (fault when the driver is not detected for 30 consecutive seconds).
Gree C2: Communication malfunction between the main control and the inverter compressor driver (fault when the driver is not detected for 30 consecutive seconds). This fault noticeably affects operation.
Possible causes
- The communication cables between the outdoor unit's main board and the inverter compressor driver inside the module are connected improperly.
- The inverter compressor driver operates improperly.
- The main board operates improperly.
Check steps
- Check whether the communication cables between the outdoor unit's main board and the compressor drive board are connected properly; if not, connect them properly.
- Check whether the compressor drive board is normal; if not, replace it.
- If cable and drive board are fine, the main control board may be abnormal – replace it.
Affected parts
- Kommunikationsleitung
- Inverter-Platine
- Hauptplatine Außengerät
Safety note
Manufacturer warning (manual PDF p. 12): before performing operations on the unit (such as commissioning, maintenance and repair), shut the unit down and cut off the power; use a suitable instrument to ensure that the voltage at the power input terminals is zero and that the power indicator on the main board is off. Otherwise an electric shock or injury may be caused. Manufacturer note (ibid.): in standby the power indicators on the main board and the drive board are on. General safety note (not from the manufacturer's manual): secure against reconnection. Lit or unlit indicators alone are no proof of absence of voltage. Dangerous voltage (DC bus) may remain on the drive board/IPM after switch-off; the manual gives no general discharge time. The absence of voltage must be confirmed by measurement on site by a qualified electrician or specialist contractor. The steps reproduce the manufacturer's troubleshooting and are not a binding work instruction; any parts replacement is decided on site by the specialist contractor/Meister.
Source: Gree GMV6 DC Inverter VRF Units Service Manual GC202005-I (AB, 380-415V 3N~ 50/60Hz, GMV-224…615WM/H-X), Fehlerliste PDF s.70-73, Abschnitt 2.28 PDF s.88-89 (basılı 86-87); Warnhinweis PDF s.12 (basılı 10)
Reviewed by Anıl Güzeldemir — in the refrigeration machine room since 2005, developer of Enthalio.