Gree H3
Medium
GMV6 — Reset protection of the fan drive module (code H3 on the 2-digit LED of the outdoor unit's main board; sub-code of H0).
Gree H3: Reset protection of the fan drive module (code H3 on the 2-digit LED of the outdoor unit's main board; sub-code of H0). This fault usually isn't an immediate stop, but should be checked soon.
Possible causes
- The fan drive board operates improperly.
Check steps
- Power the fan drive board off and on; if the fault persists after more than three power cycles, check whether P3 is displayed at the same time.
- If P3 is displayed at the same time: the compressor drive board is abnormal – replace it. Otherwise: the fan drive board is abnormal – replace it.
Affected parts
Safety note
Manufacturer warning (manual PDF p. 12): before performing operations on the unit (such as commissioning, maintenance and repair), shut the unit down and cut off the power; use a suitable instrument to ensure that the voltage at the power input terminals is zero and that the power indicator on the main board is off. Otherwise an electric shock or injury may be caused. Manufacturer note (ibid.): in standby the power indicators on the main board and the drive board are on. General safety note (not from the manufacturer's manual): secure against reconnection. Lit or unlit indicators alone are no proof of absence of voltage. Dangerous voltage (DC bus) may remain on the drive board/IPM after switch-off; the manual gives no general discharge time. The absence of voltage must be confirmed by measurement on site by a qualified electrician or specialist contractor. The steps reproduce the manufacturer's troubleshooting and are not a binding work instruction; any parts replacement is decided on site by the specialist contractor/Meister. Power-cycle only to the extent described in the manual; if the fault persists, have the cause checked by a specialist contractor instead of restarting again.
Source: Gree GMV6 DC Inverter VRF Units Service Manual GC202005-I (AB, 380-415V 3N~ 50/60Hz, GMV-224…615WM/H-X), Fehlerliste PDF s.70-73, Abschnitt 2.81 PDF s.130 (basılı 128); Warnhinweis PDF s.12 (basılı 10)