Fault Codes / Gree / F5
GR
Gree F5
High
GMV6 — Malfunction of the discharge temperature sensor of compressor 1.
Gree F5: Malfunction of the discharge temperature sensor of compressor 1. This fault noticeably affects operation.
Possible causes
- Poor contact between the discharge temperature sensor and the main board interface.
- Abnormal discharge temperature sensor.
- Abnormal detection circuit.
Check steps
- Check whether the interface terminal between the main board and the temperature sensor is loose or contains foreign matter; remove the foreign matter and plug it in tightly.
- If the fault persists: replace the temperature sensor.
- If it still persists, the detection circuit may operate improperly: replace the main control board.
Affected parts
- Druckgasfühler
- Hauptplatine Außengerät
Safety note
Manufacturer warning (manual PDF p. 12): before performing operations on the unit (such as commissioning, maintenance and repair), shut the unit down and cut off the power; use a suitable instrument to ensure that the voltage at the power input terminals is zero and that the power indicator on the main board is off. Otherwise an electric shock or injury may be caused. Manufacturer note (ibid.): in standby the power indicators on the main board and the drive board are on. General safety note (not from the manufacturer's manual): secure against reconnection. Lit or unlit indicators alone are no proof of absence of voltage. Dangerous voltage (DC bus) may remain on the drive board/IPM after switch-off; the manual gives no general discharge time. The absence of voltage must be confirmed by measurement on site by a qualified electrician or specialist contractor. The steps reproduce the manufacturer's troubleshooting and are not a binding work instruction; any parts replacement is decided on site by the specialist contractor/Meister.
Source: Gree GMV6 DC Inverter VRF Units Service Manual GC202005-I (AB, 380-415V 3N~ 50/60Hz, GMV-224…615WM/H-X), Fehlerliste PDF s.70-73, Abschnitt 2.64 PDF s.114 (basılı 112); Warnhinweis PDF s.12 (basılı 10)