Fault Codes / Gree / C0
GR
Gree C0
High
GMV6 — Communication malfunction between indoor and outdoor units and between the indoor unit and its wired controller (per manual: no communication for 30 seconds).
Gree C0: Communication malfunction between indoor and outdoor units and between the indoor unit and its wired controller (per manual: no communication for 30 seconds). This fault noticeably affects operation.
Possible causes
- Communication cables are connected wrongly or have come loose.
- Communication cables are broken.
- Poor contact of the communication cables.
- The number of connected wired controllers or their addresses are set improperly.
- A controller operates improperly.
Check steps
- Evaluate where C0 is shown: if the outdoor unit's main board does not show C0, check the connection between indoor unit and wired controller; if the outdoor main board, the indoor unit's receiver and the wired controller show C0, check the connections indoor–outdoor unit and indoor unit–wired controller; if only the wired controller shows C0, check its connection, the number of wired controllers and the address settings.
- Check the communication cables for wrong connection or looseness, breaks and poor contact with the terminal block; connect properly or replace the cable.
- Wired controllers: no more than two connected to an indoor unit at the same time; with two, assign different addresses; with one, set it as the primary controller (manual PDF p. 88).
- If the fault persists, the outdoor unit's main control board, the indoor unit's main control board or the wired controller may be abnormal – replace the part concerned.
Affected parts
- Kommunikationsleitung
- Kabelfernbedienung
- Hauptplatine Innengerät
- Hauptplatine Außengerät
Safety note
Manufacturer warning (manual PDF p. 12): before performing operations on the unit (such as commissioning, maintenance and repair), shut the unit down and cut off the power; use a suitable instrument to ensure that the voltage at the power input terminals is zero and that the power indicator on the main board is off. Otherwise an electric shock or injury may be caused. Manufacturer note (ibid.): in standby the power indicators on the main board and the drive board are on. General safety note (not from the manufacturer's manual): secure against reconnection. Lit or unlit indicators alone are no proof of absence of voltage. Dangerous voltage (DC bus) may remain on the drive board/IPM after switch-off; the manual gives no general discharge time. The absence of voltage must be confirmed by measurement on site by a qualified electrician or specialist contractor. The steps reproduce the manufacturer's troubleshooting and are not a binding work instruction; any parts replacement is decided on site by the specialist contractor/Meister.
Source: Gree GMV6 DC Inverter VRF Units Service Manual GC202005-I (AB, 380-415V 3N~ 50/60Hz, GMV-224…615WM/H-X), Fehlerliste PDF s.70-73, Abschnitt 2.27 PDF s.87-88 (basılı 85-86); Warnhinweis PDF s.12 (basılı 10)