Fault Codes / Gree / P0
GR
Gree P0
Critical
GMV6 — Malfunction of the compressor drive board (parent code on the indoor unit's wired controller); the specific fault is shown on the 2-digit LED of the outdoor unit's main board.
Gree P0: Malfunction of the compressor drive board (parent code on the indoor unit's wired controller); the specific fault is shown on the 2-digit LED of the outdoor unit's main board. This fault typically halts operation and needs immediate attention.
Possible causes
- Compressor drive module reset protection (LED P3).
- Temperature sensor fault of the compressor drive (LED P7).
- IPM over-temperature protection of the compressor drive (LED P8).
- Current detection circuit fault of the compressor drive (LED PC).
- Charging loop fault of the compressor drive (LED PF).
- Loss of synchronization of the inverter compressor (LED P9).
- Inverter compressor startup failure (LED PJ).
Check steps
- Confirm the code on the indoor unit's wired controller (P0).
- At the same time read the code on the 2-digit LED of the outdoor unit's main board; it identifies the specific fault (P3, P7, P8, PC, PF, P9 or PJ).
- Troubleshoot according to this LED sub-code; PC is listed in this app under “Pc”.
Safety note
Manufacturer warning (manual PDF p. 12): before performing operations on the unit (such as commissioning, maintenance and repair), shut the unit down and cut off the power; use a suitable instrument to ensure that the voltage at the power input terminals is zero and that the power indicator on the main board is off. Otherwise an electric shock or injury may be caused. Manufacturer note (ibid.): in standby the power indicators on the main board and the drive board are on. General safety note (not from the manufacturer's manual): secure against reconnection. Lit or unlit indicators alone are no proof of absence of voltage. Dangerous voltage (DC bus) may remain on the drive board/IPM after switch-off; the manual gives no general discharge time. The absence of voltage must be confirmed by measurement on site by a qualified electrician or specialist contractor. The steps reproduce the manufacturer's troubleshooting and are not a binding work instruction; any parts replacement is decided on site by the specialist contractor/Meister. If an LED sub-code has no entry of its own in this app: do not bypass or disable protective devices; consult the manufacturer's manual or a specialist contractor.
Source: Gree GMV6 DC Inverter VRF Units Service Manual GC202005-I (AB, 380-415V 3N~ 50/60Hz, GMV-224…615WM/H-X), Fehlerliste PDF s.70-73, Abschnitt 2.125 PDF s.161 (basılı 159); Warnhinweis PDF s.12 (basılı 10)
Reviewed by Anıl Güzeldemir — in the refrigeration machine room since 2005, developer of Enthalio.