Fault Codes / Gree / P2
GR
Gree P2
Critical
GMV6 — Input voltage protection of the compressor drive board (parent code on the indoor unit's wired controller); the specific fault is shown on the 2-digit LED of the outdoor unit's main board.
Gree P2: Input voltage protection of the compressor drive board (parent code on the indoor unit's wired controller); the specific fault is shown on the 2-digit LED of the outdoor unit's main board. This fault typically halts operation and needs immediate attention.
Possible causes
- Over-voltage protection of the compressor drive DC bus (LED PH); per manual triggered when the input voltage exceeds 460 V (PDF p. 169).
- Under-voltage protection of the compressor drive DC bus (LED PL); per manual triggered when the input voltage is below 320 V (PDF p. 170).
Check steps
- Confirm the code on the indoor unit's wired controller (P2).
- At the same time read the code on the 2-digit LED of the outdoor unit's main board; it identifies the specific fault (PH or PL).
- Troubleshoot according to this LED sub-code: per manual, PH checks whether the unit's input voltage exceeds 460 V and PL whether it is below 320 V (PDF p. 170); if not, the manual points to the compressor drive board.
Safety note
Manufacturer warning (manual PDF p. 12): before performing operations on the unit (such as commissioning, maintenance and repair), shut the unit down and cut off the power; use a suitable instrument to ensure that the voltage at the power input terminals is zero and that the power indicator on the main board is off. Otherwise an electric shock or injury may be caused. Manufacturer note (ibid.): in standby the power indicators on the main board and the drive board are on. General safety note (not from the manufacturer's manual): secure against reconnection. Lit or unlit indicators alone are no proof of absence of voltage. Dangerous voltage (DC bus) may remain on the drive board/IPM after switch-off; the manual gives no general discharge time. The absence of voltage must be confirmed by measurement on site by a qualified electrician or specialist contractor. The steps reproduce the manufacturer's troubleshooting and are not a binding work instruction; any parts replacement is decided on site by the specialist contractor/Meister. If an LED sub-code has no entry of its own in this app: do not bypass or disable protective devices; consult the manufacturer's manual or a specialist contractor. Live measurements (e.g. of the input voltage) only by a qualified electrician in accordance with the applicable rules.
Source: Gree GMV6 DC Inverter VRF Units Service Manual GC202005-I (AB, 380-415V 3N~ 50/60Hz, GMV-224…615WM/H-X), Fehlerliste PDF s.70-73, Abschnitt 2.127 PDF s.162 (basılı 160); Abschnitte 2.135/2.136 (PH/PL) PDF s.169-170 (basılı 167-168); Warnhinweis PDF s.12 (basılı 10)
Reviewed by Anıl Güzeldemir — in the refrigeration machine room since 2005, developer of Enthalio.
Look up in Enthalio →