Fault Codes / Gree / H8
GR
Gree H8
High
GMV6 — Drive IPM high-temperature (over-temperature) protection of the fan (shown on the 2-digit LED of the outdoor unit's main board; sub-code of H0).
Gree H8: Drive IPM high-temperature (over-temperature) protection of the fan (shown on the 2-digit LED of the outdoor unit's main board; sub-code of H0). This fault noticeably affects operation.
Possible causes
- The IPM module is not covered, unevenly covered or covered by dried thermal grease.
- The IPM module's screws are not tightened.
- The fan drive board operates improperly.
Check steps
- Check whether the drive board screws are tightened and the IPM module is coated with thermal grease; if not: tighten the screws and coat the cooling plate with thermal grease.
- If the IPM over-temperature protection is triggered upon power-on: the fan drive board is abnormal – replace it.
Affected parts
Safety note
Manufacturer warning (manual PDF p. 12): before performing operations on the unit (such as commissioning, maintenance and repair), shut the unit down and cut off the power; use a suitable instrument to ensure that the voltage at the power input terminals is zero and that the power indicator on the main board is off. Otherwise an electric shock or injury may be caused. Manufacturer note (ibid.): in standby the power indicators on the main board and the drive board are on. General safety note (not from the manufacturer's manual): secure against reconnection. Lit or unlit indicators alone are no proof of absence of voltage. Dangerous voltage (DC bus) may remain on the drive board/IPM after switch-off; the manual gives no general discharge time. The absence of voltage must be confirmed by measurement on site by a qualified electrician or specialist contractor. The steps reproduce the manufacturer's troubleshooting and are not a binding work instruction; any parts replacement is decided on site by the specialist contractor/Meister.
Source: Gree GMV6 DC Inverter VRF Units Service Manual GC202005-I (AB, 380-415V 3N~ 50/60Hz, GMV-224…615WM/H-X), Fehlerliste PDF s.70-73, Abschnitt 2.85 PDF s.134 (basılı 132); Warnhinweis PDF s.12 (basılı 10)