Fault Codes / Gree / P7
GR
Gree P7
High
GMV6 — Malfunction of the drive temperature sensor of the compressor drive board (shown on the 2-digit LED of the outdoor unit's main board; sub-code of P0).
Gree P7: Malfunction of the drive temperature sensor of the compressor drive board (shown on the 2-digit LED of the outdoor unit's main board; sub-code of P0). This fault noticeably affects operation.
Possible causes
- The compressor drive board operates improperly.
Check steps
- Power the unit off and on; if the fault persists after more than three power cycles: the compressor drive board operates improperly – replace it.
Affected parts
Safety note
Manufacturer warning (manual PDF p. 12): before performing operations on the unit (such as commissioning, maintenance and repair), shut the unit down and cut off the power; use a suitable instrument to ensure that the voltage at the power input terminals is zero and that the power indicator on the main board is off. Otherwise an electric shock or injury may be caused. Manufacturer note (ibid.): in standby the power indicators on the main board and the drive board are on. General safety note (not from the manufacturer's manual): secure against reconnection. Lit or unlit indicators alone are no proof of absence of voltage. Dangerous voltage (DC bus) may remain on the drive board/IPM after switch-off; the manual gives no general discharge time. The absence of voltage must be confirmed by measurement on site by a qualified electrician or specialist contractor. The steps reproduce the manufacturer's troubleshooting and are not a binding work instruction; any parts replacement is decided on site by the specialist contractor/Meister. Power-cycle only to the extent described in the manual; if the fault persists, have the cause checked by a specialist contractor instead of restarting again.
Source: Gree GMV6 DC Inverter VRF Units Service Manual GC202005-I (AB, 380-415V 3N~ 50/60Hz, GMV-224…615WM/H-X), Fehlerliste PDF s.70-73, Abschnitt 2.131 PDF s.166 (basılı 164); Warnhinweis PDF s.12 (basılı 10)