Fault Codes / LG / CH62
Multi V5 — High temperature at the outdoor unit inverter PCB heat sink.
LG CH62: High temperature at the outdoor unit inverter PCB heat sink. This fault noticeably affects operation.
Source: LG resmi servis kilavuzu (bagimsiz cift-dogrulandi) — LG Multi V5 Service Manual (ManualsLib doc #1483751), Error No. 62, page 172 (not page 126 as originally cited — page 126 only lists codes 01-09): "High temperature at the outdoor unit inverter PCB heat sink." Trigger: heatsink temp exceeds 257°F (~125°C). Variants: Master 621, Slave1 622, Slave2 623.
Reviewed by Anıl Güzeldemir — in the refrigeration machine room since 2006, developer of Enthalio.