Fault Codes / Bosch / A01 (5994)

BO

Bosch A01 (5994)

High

Compress — Low pressure in brine circuit (ground source).

Bosch A01 (5994): Low pressure in brine circuit (ground source). This fault noticeably affects operation.

Possible causes

Check steps

Affected parts

Safety note

Brine — antifreeze; wear skin protection.

Source: Bosch resmi servis kılavuzu — Doc: 'A01 Installer Info: Low pressure in brine circuit. The pressure guard for the cold carrier circuit has tripped (normally open circuit). Pressure limit is 0.5 bar. Leakage or unsufficiently filled cold carrier circu

Reviewed by Anıl Güzeldemir — in the refrigeration machine room since 2006, developer of Enthalio.

Look up in Enthalio →

Related fault codes

No EMS BUS communication / internal connectionA11 Booster heater limiter (STB) or pressure switcA01 (5246) Hot gas temperature too high (TR6 > 110–120H01 (5311) Z1 phase monitor tripped: one or more supply-vA01 (5273) High pressure guard MR1 tripped.H01 (5508) Compressor control failure – not running / locA01 (5350)