ENTHALIO

Fault Codes / Bosch / A01 (5981)

BO

Bosch A01 (5981)

Critical

Compress — Wrong rotation direction in compressor.

Bosch A01 (5981): Wrong rotation direction in compressor. This fault typically halts operation and needs immediate attention.

Possible causes

Check steps

Affected parts

Safety note

400V — isolate power.

Source: Bosch resmi servis kılavuzu — Doc: 'A01 Installer Info: Incorrect running direction of compressor... triggered if condensing pressure has not increased by least 0.5 bar in 10 s after run signal... Wrong rotation direction in compressor.'

Reviewed by Anıl Güzeldemir — in the refrigeration machine room since 2006, developer of Enthalio.

Look up in Enthalio →

Related fault codes

No EMS BUS communication / internal connectionA11 Booster heater limiter (STB) or pressure switcA01 (5246) Hot gas temperature too high (TR6 > 110–120H01 (5311) Z1 phase monitor tripped: one or more supply-vA01 (5273) High pressure guard MR1 tripped.H01 (5508) Compressor control failure – not running / locA01 (5350)