Trane — Fault Codes
22 codes
—
1
— High pressure cutout. Condensing pressure exceeded the safety limit.
2
— Low pressure cutout. Suction pressure too low.
5
— Oil failure. Inadequate oil pressure or flow in compressor.
CGAM / RTAC
100
— Low suction superheat — liquid floodback risk.
101
— High pressure limit mode active.
103
— High pressure cutout (HPS).
105
— Low pressure cutout (LPS).
110
— Excessive loss of communication / bus error.
125
— Phase loss / phase sequence wrong.
70
— Evaporator entering water sensor fault.
71
— Evaporator leaving water sensor fault.
Tracer CH530 (CGAM/CXAM)
BAS Communication Lost
— BAS was set up as installed and communication with the LCI-C was lost for 15 continuous minutes.
Check Clock
— The real time clock has detected loss of its oscillator at some time in the past (e.g. dead backup battery).
Compressor Fault
— The compressor fault switch input is open.
Compressor Fault Lockout
— Compressor fault switch input remained open for more than 35 minutes, or 5 events occurred within 210 minutes — lockout.
High Discharge Temperature
— The discharge temperature exceeded the limits for the compressor.
High Discharge Temperature Lockout
— 5 high discharge temperature diagnostics occurred over 210 minutes — lockout.
LCI-C Software Mismatch
— LCI-C Neuron software and LCI-C IPC3 software do not match.
Low Pressure Cutout
— The suction refrigerant pressure fell below the low pressure cutout trip point.
MP: Non-Volatile Block Test Error
— Main processor has determined there was an error with a block in the non-volatile memory.
Phase Protection Fault
— Phase protection module recognized a phase loss or phase reversal of the line power.
Very Low Suction Pressure
— A circuit's suction pressure dropped below 50% of the low pressure cutout setpoint — forces an entire chiller shutdown.