ENTHALIO

Fault Codes / Samsung / E231

SA

Samsung E231

Medium

DVM / Split — Outdoor condenser (COND) temperature sensor fault.

Samsung E231: Outdoor condenser (COND) temperature sensor fault. This fault usually isn't an immediate stop, but should be checked soon.

Possible causes

Check steps

Affected parts

Safety note

230V — isolate power.

Source: Samsung resmi servis kılavuzu — Samsung AM036NXMDCR Service Manual p.50 / AM036FXMDCH Service Manual p.25 "Outdoor Temperature Sensor Error (Open/Short) (Error Code: E221, E231, E251, E269...)": E231 = condenser (COND OUT) outdoor temperature sensor open/short, trip levels >4.9V(-50°C) or <0.4V(93°C). Matches a…

Reviewed by Anıl Güzeldemir — in the refrigeration machine room since 2006, developer of Enthalio.

Look up in Enthalio →

Related fault codes

Indoor/outdoor communication error.E101 Room temperature sensor (Room-TH) fault.E121 Indoor fan error.E154 Discharge temperature too high (DIS-TH over).E416 Outdoor EEV (expansion valve) self-diagnosis eE422 Communication error indoor ↔ outdoor (trackingE102