Lennox — Fault Codes
26 codes
—
115
— High pressure 1. Comp 1 high pressure lockout.
LMC / Compactor
12
— Low pressure switch tripped.
13
— High pressure switch tripped.
18
— Compressor protection module trip.
30
— Water flow switch open.
42
— Evaporator freeze protection active.
45
— Phase monitor trip.
Mini-Split MWM/MPA (Außeneinheit)
E0
— Outdoor EEPROM malfunction — main control board is not receiving feedback from the EEPROM chip.
E3
— Communication error between outdoor unit main control and integrated power module (IPM), no feedback for 60 seconds.
E4
— Indoor unit coil outlet temperature sensor (T2) error — voltage outside 0.06-4.94V range.
E5
— High or low voltage protection active.
E6
— Power Factor Correction (PFC) module protection (MPA036S4M-1P and MPA048S4M-1P only).
E8
— Outdoor DC fan motor speed error.
F1
— Outdoor coil sensor (T3) error — voltage outside 0.06-4.94V range.
F2
— Outdoor ambient sensor (T4) error — voltage outside 0.06-4.94V range.
F3
— Compressor discharge sensor (T5) error — voltage outside 0.06-4.94V range.
P1
— High pressure switch open — trips at 639 PSI and resets at 464 PSI.
P2
— Low pressure switch open — trips at 20 PSI and resets at 43 PSI.
P3
— Outdoor compressor current overload sensed.
P4
— High temperature sensed at compressor discharge line.
P5
— High temperature sensed at outdoor coil (T3).
P6
— Integrated power module (IPM) error.
P7
— IPM module temperature sensor malfunction.
Mini-Split MWM/MPA (Inneneinheit)
CP
— Condensate switch (water level) alarm malfunction (M22A, M33A/B and MMDA units only).
EC
— Low refrigerant error.
EE
— Indoor Unit EEPROM malfunction.