Toshiba — Fault Codes
83 codes
MiNi-SMMS
E01
— Communication error (remote controller).
Multi-Type (SVM-21073)
E01
— No master remote control / failure receiving signal — signals cannot be received from the indoor unit.
E02
— Failure remote control — signals cannot be transmitted to the indoor unit.
E03
— Indoor-remote controller periodic communication error — from remote controller or network adaptor.
E09
— Duplicated master remote control — both remote controllers have been set as master.
E10
— Communication trouble between main MCU and the fan motor.
E17
— Communication trouble between flow selector (FS) unit(s) — no communication from FS unit(s).
E18
— Periodic communication error between indoor header unit and other group units.
F01
— Indoor heat exchanger temperature sensor (TCJ) has been open/shorted.
F02
— Indoor heat exchanger temperature sensor (TC2) has been open/shorted.
F03
— Indoor heat exchanger temperature sensor (TC1) has been open/shorted.
F11
— Discharge temperature sensor (TF) has been open/shorted.
F30
— Occupancy sensor trouble has been detected.
L03
— Duplicated indoor group header — more than one header unit in the group.
L07
— Connection of group control cable error — there is at least one indoor unit to which group wiring is not connected.
L09
— Indoor capacity not set.
SMMS / SMMS-e
E04
— Indoor ↔ outdoor communication: no signal from outdoor.
E06
— No communication to indoor unit
E07
— Outdoor: transmission circuit error to indoor.
E08
— Duplicated indoor address.
E12-02
— Auto-addressing: outdoor-↔-outdoor line error.
E16
— Too many indoor units / capacity exceeded.
E19
— Outdoor header unit count error (0 or ≥2).
E19-02
— Two or more outdoor header units in one line.
E20
— Other line detected during auto-addressing.
E23
— Outdoor ↔ outdoor communication error.
E26
— Signal loss from an outdoor follower unit.
E28
— Follower outdoor unit error (sub-code = unit no.).
E31
— IPDU communication error (inverter box).
F04
— Discharge temp sensor TD1 fault.
F06
— Heat exchanger temp sensor TE fault.
F06-02
— Heat exchanger liquid sensor TE2 (2nd circuit) open/short.
F07
— Liquid line temp sensor TL fault.
F07-02
— Liquid line sensor TL2 (2nd circuit) open/short.
F08
— Outside air temp sensor TO fault.
F09-01
— Heat exchanger gas sensor TG1 open/short.
F10
— Indoor room air (TA) sensor fault.
F12
— Suction temp sensor TS fault.
F23
— Low pressure sensor (Ps) output abnormal.
F24
— High pressure sensor (Pd) faulty / abnormal readings.
F29
— Indoor EEPROM error.
F31
— Outdoor EEPROM error (header).
H02
— Compressor lock / overcurrent shutdown.
H03-01
— Current sensor fault compressor 1.
H03-02
— Current sensor fault compressor 2.
H06
— Low pressure protection triggered.
H06-01
— Low pressure sensor (Ps) abnormal reading.
H07
— Low oil level protection.
H07-01
— Low oil level protection (TK1/TK2 oil temp).
H08
— Oil temperature sensor (TK1/TK2) fault.
H08-01
— Oil temperature sensor TK1 fault.
H08-02
— Oil temperature sensor TK2 fault.
H16-01
— Oil circuit trouble TK1 (oil level detection) despite compressor run.
H16-02
— Oil circuit trouble TK2 despite compressor run.
L04
— Duplicated outdoor line address.
L08
— Indoor group/address not set.
L29
— IPDU quantity error (CF).
L29-01
— Number of detected IPDU units reduced.
L30
— Indoor external interlock triggered.
P03
— Discharge temperature high (TD1 > 115°C)
P03-01
— Discharge temperature TD1 too high (>115 °C).
P04
— Outdoor unit high pressure fault.
P04-01
— High pressure switch HPS active (compressor 1).
P05
— Open phase / power supply fault (outdoor).
P05-01
— Inverter DC-link voltage (Vdc) abnormal — low.
P07
— Heat sink overheat (TH) — power module.
P07-01
— Inverter heat sink overheat (poor IGBT cooling).
P07-04
— Heat sink: dew condensation (moisture at heatsink).
P10
— Indoor condensate overflow (float switch).
P12
— Indoor DC fan motor error.
P17
— Discharge temperature TD2 error.
P19
— 4-way valve error
P20
— High pressure protection (Pd) triggered.
P20-01
— High pressure protection — compressor 1.
P20-02
— High pressure protection — compressor 2.
P22
— Outdoor fan IPDU (driver) error
P22-01
— Outdoor fan IPDU fault (fan 1).
P22-02
— Outdoor fan IPDU fault (fan 2).
P26
— G-Tr (IGBT) short-circuit protection / compressor overcurrent.
P26-01
— G-Tr (IGBT) short-circuit protection — compressor 1.
P26-02
— G-Tr (IGBT) short-circuit protection — compressor 2.
P29
— Compressor error (position detection)
P29-01
— Compressor position detection circuit fault.