Midea — Fault Codes
57 codes
—
E0
— Mode conflict — indoor units set to different operating modes.
E1
— Communication error between indoor and outdoor units.
E4
— Indoor ambient or pipe temperature sensor fault (open or short circuit).
F1
— DC bus voltage protection (inverter).
P1
— High pressure protection (refrigerant overcharge or blockage).
P2
— Low pressure protection (refrigerant leak or lack of airflow).
P4
— Compressor discharge pipe high temperature protection.
V6/V8
C0
— Fan motor failed or feedback abnormal.
C1
— Electronic expansion valve not responding.
C2
— Condensate overflow or float switch activated.
C3
— Indoor control board internal error.
C5
— Built-in sensor in remote controller failed.
C7
— PL protection occurred three times in 100 minutes (repeated inverter module temperature protection).
E2
— Condenser fan motor failed or drawing excessive current.
E3
— Reversing valve not switching correctly.
E5
— Insufficient refrigerant.
E6
— Oil not returning to compressor.
E7
— Main outdoor control board error.
E8
— System configuration error.
E9
— EEPROM mismatch (compressor system) — manual restart required.
F0
— Communication error outdoor ↔ indoor units.
F2
— Wired remote lost communication with indoor unit.
F3
— Plate heat exchanger cooling refrigerant outlet temperature sensor (T6B) error.
F4
— Indoor unit address conflict or not configured.
F5
— Internal PCB communication within outdoor unit failed.
F6
— Electronic expansion valve connection error.
H0
— Communication error between main control chip and inverter driver chip.
H1
— Indoor pipe temperature sensor fault.
H2
— Indoor discharge sensor fault.
H3
— Outdoor air temperature sensor fault.
H4
— Discharge temperature sensor fault.
H5
— Suction temperature sensor fault.
H6
— Heat exchanger temperature sensor fault.
H7
— CT sensor fault.
H8
— High pressure sensor fault.
H9
— Low pressure sensor fault.
Hd
— Slave unit malfunction (displayed on the master unit only).
L0
— Inverter module protection.
L1
— DC bus low voltage protection.
L2
— DC bus high voltage protection.
L4
— MCE error (compressor commutation error).
L5
— Zero speed protection (compressor fails to start rotating).
L7
— Phase sequence error (compressor inverter side).
L8
— Compressor frequency variation greater than 15Hz within one second — protection.
L9
— Actual compressor frequency differs from target frequency by more than 15Hz — protection.
P0
— Discharge pressure exceeded high pressure limit.
P3
— Compressor discharge temperature exceeded safe limit.
P5
— Inverter heatsink exceeded safe temperature.
P6
— Compressor failed to start.
P7
— Incorrect phase sequence or phase loss.
P8
— Compressor frequency exceeded maximum.
P9
— Indoor coil temperature dropped too low.
Pb
— DC link voltage too high.
Pc
— DC link voltage too low.
Pd
— System operating beyond design capacity.
PL
— Inverter module temperature protection.
PP
— Compressor discharge insufficient superheat protection.