Fault Codes / Hitachi / 43

HIT

Hitachi 43

Critical

Set Free Sigma / IVX (FSXN) — Activation of the low compression ratio protection device

Hitachi 43: Activation of the low compression ratio protection device This fault typically halts operation and needs immediate attention.

Possible causes

Check steps

Affected parts

Safety note

High-pressure refrigerant circuit — safely relieve pressure before intervention, wear protective equipment.

Source: Hitachi resmi servis kılavuzu (bağımsız çift-doğrulandı) — Hitachi FSXN Series Service Manual, Troubleshooting by alarm code, p.222 (manualslib.com/manual/2375584, page=222): Alarm code 43 — "Excessively Low Compression Ratio" — "Activation of the low compression ratio protection device." Ɛ = (Pd+0.1)/(Ps+0.06); condition Ɛ < 1.8 occurring three times within one hour trigg…

Reviewed by Anıl Güzeldemir — in the refrigeration machine room since 2006, developer of Enthalio.

Look up in Enthalio →