Fault Codes / Copeland / 6 Flashes
CoreSense — Open Start Circuit — module detects a demand signal and current in the 'R' winding, but no current in the 'S' winding for 2 seconds (Flash Code 6, red, immediate lockout).
Copeland 6 Flashes: Open Start Circuit — module detects a demand signal and current in the 'R' winding, but no current in the 'S' winding for 2 seconds (Flash Code 6, red, immediate lockout). This fault usually isn't an immediate stop, but should be checked soon.
Source: Emerson AE8-1385 CoreSense Diagnostics for Copeland Scroll UltraTech Compressors (2011), Code 6 description, p.5
Reviewed by Anıl Güzeldemir — in the refrigeration machine room since 2006, developer of Enthalio.