Fault Codes / Copeland / 10 Flashes

CO

Copeland 10 Flashes

Critical

CoreSense — Over-Current Protection — current at the PROT terminal exceeds 2A for 40ms; module is mis-wired or the contactor coil is shorted to ground (Flash Code 10, red, not listed on the module label).

Copeland 10 Flashes: Over-Current Protection — current at the PROT terminal exceeds 2A for 40ms; module is mis-wired or the contactor coil is shorted to ground (Flash Code 10, red, not listed on the module label). This fault typically halts operation and needs immediate attention.

Possible causes

Check steps

Affected parts

Safety note

Isolate power before testing.

Source: Emerson AE8-1385 CoreSense Diagnostics for Copeland Scroll UltraTech Compressors (2011), Code 10 description, p.5

Reviewed by Anıl Güzeldemir — in the refrigeration machine room since 2006, developer of Enthalio.