Fault Codes / Copeland / 10 Flashes
CoreSense — Over-Current Protection — current at the PROT terminal exceeds 2A for 40ms; module is mis-wired or the contactor coil is shorted to ground (Flash Code 10, red, not listed on the module label).
Copeland 10 Flashes: Over-Current Protection — current at the PROT terminal exceeds 2A for 40ms; module is mis-wired or the contactor coil is shorted to ground (Flash Code 10, red, not listed on the module label). This fault typically halts operation and needs immediate attention.
Source: Emerson AE8-1385 CoreSense Diagnostics for Copeland Scroll UltraTech Compressors (2011), Code 10 description, p.5
Reviewed by Anıl Güzeldemir — in the refrigeration machine room since 2006, developer of Enthalio.