Temp °CBubble point (bar)Dew point (bar)
-501.04771.0032
-481.15661.108
-461.27431.2211
-441.40131.3433
-421.53811.4749
-401.68511.6164
-381.84291.7683
-362.01211.9312
-342.19322.1056
-322.38672.292
-302.59322.4911
-282.81332.7033
-263.04752.9292
-243.29663.1695
-223.5613.4247
-203.84153.6955
-184.13863.9824
-164.4534.2862
-144.78534.6074
-125.13624.9466
-105.50635.3047
-85.89655.6822
-66.30726.0799
-46.73936.4984
-27.19346.9384
07.67027.4007
28.17067.886
48.69518.395
69.24478.9286
89.81999.4874
1010.421610.0723
1211.050610.6841
1411.707611.3235
1612.393511.9915
1813.10912.6888
2013.85513.4163
2214.632414.175
2415.441914.9656
2616.284415.7892
2817.160816.6466
3018.072117.5389
3219.019118.4671
3420.002719.4321
3621.023920.435
3822.083821.477
4023.183222.5591
4224.323323.6826
4425.50524.8487
4626.729526.0587
4827.997927.3138
5029.311428.6156
5230.671229.9656